Feature:

Electrical isolation: 1500VAC(Input/Output)
• Universal temperature input,programmable flexibly
Input signal:8 types of thermocouples, 2 types of RTD • Built-in cold junction compensation for thermocouple input. • Input Type can be programmable flexibly by PC Softwa • Hart communicator configurable with software Output:4-20mA,2 wire+Hart Protocal
• Power supply:24 VDC

Specification Details
Accuracy0.1 FS
Electrical isolation1500VAC
Response time700 ms up to 90% of final value
Input typeThermocouple, RTD
Cold junction compensation-20 to 60°C
Compensation Accuracy±1°C
Temperature shift0.0075%FS/°C
Output4-20 mA, 2 wire; Hart protocol
Load resistanceRL ≤ (Ue-12)/0.021
Current outputIH = 21mA, IL = 3.8mA (When high-low alarming limiting over)
Current when alarmingConfigurable (when input in open circuit)
Earthquake resistance4g/2 to 150 Hz
Max Loadmax(V power supply -7.5V)/0.022A (current output)
InstallationHead of B type box
IP protectionP00; IP66 (mounted)
Input Type Temperature Range Min. Range
RTD Pt100 -200 to 600°C 10°C
CU50 -50 to 150°C 10°C
TC B 400 to 1820°C 500°C
E -100 to 1000°C 50°C
J -100 to 1200°C 50°C
K -180 to 1372°C 50°C
N -180 to 1300°C 50°C
R -50 to 1768°C 500°C
S -50 to 1768°C 500°C
T -200 to 400°C 50°C